Vue de la page 0
1
1
RC-100BZ Heat Pump
2 Stage Heat / 1 Stage Cool
Thermostat Installation Instructions
DESCRIPTION
The RC-100BZ is a precision digital thermostat designed for 24 VAC heat pump systems. It has the capability
of being controlled both locally and by remote control over a Z-Wave network. It offers programmability,
stand-alone operation, and communications with automation systems, utility control systems, or personal
computers over a Z-Wave network. The RC-100ZB is equipped with a “cool blue” backlight display.
Electrical rating: 24 V; 3 A; 50/60 Hz
Maximum current: 2 A on any circuit, 3 A total
Thermostat operating current: less than 15 mA
The following requirements must be observed for installation in Europe: CE
1. This equipment must be installed in accordance with National wiring rules for the country in which it is
installed.
2. Fuses must be replaced only with IEC rated components.
3. All product labels, instructions and markings relating to safety must be translated to a language, which is
acceptable in the country in which this equipment is to be installed.
INSTALLATION
Before installing this thermostat:
1. Read all of the installation instructions carefully.
2. Read the Owner's Manual carefully.
3. Ensure that this product is suitable for your application.
4. Ensure that wiring complies with all codes and ordinances.
5. Disconnect power to the control transformer to prevent electrical shock and damage to equipment.
6. Select an appropriate location to ensure an accurate temperature reading.
Location
When replacing an existing thermostat, install the RC-100BZ in the same location. If the existing location
doesn't meet the following criteria, choose a new location. When choosing a location for the thermostat:
1. Ensure that the thermostat is mounted 5 feet above the floor and is at least 2 feet from an outdoor wall.
2. Ensure that the thermostat is located in an area where there is adequate air circulation.
3. Do not mount in the path of direct sunlight or of radiant heat generated by appliances.
4. Do not mount behind an outdoor wall, near a fireplace, or in the path of any air ducts.
Document Number 13I00-61 / Rev A / May, 2007
Copyright © 1999-2007 Home Automation, Inc.
All Rights Reserved
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - RC-100BZ Heat Pump

11 RC-100BZ Heat Pump 2 Stage Heat / 1 Stage Cool Thermostat Installation Instructions DESCRIPTION The RC-100BZ is a precision digital thermostat d

Page 2 - Figure 1

1100 11 Cooling minimum on/off time (minutes) This item is used to limit the on and off times of the cooling system. When the cooling system starts

Page 3 - Figure 2 Figure 3

1111 15 Filter reminder The thermostat logs the amount of time the system fan has been running. When this setting reaches 0, the thermostat will dis

Page 4 - CAUTION:

1122 QUICK-REFERENCE SETUP GUIDE This table displays each Installer Setup item with its default setting. The column labeled "CURRENT" can

Page 5 - Figure 5

1133 The thermostat supports the following command classes: COMMAND_CLASS_THERMOSTAT_MODE COMMAND_CLASS_THERMOSTAT_SETPOINT COMMAND_CLASS_THERMOSTAT_

Page 6 - Figure 6

1144 COMMAND_CLASS_THERMOSTAT_OPERATING_STATE Upon power up, allow 10 seconds for the RC-100BZ thermostat to initialize. After 10 seconds, a control

Page 7

1155 TROUBLESHOOTING TIPS SYMPTOM ACTION TO TAKE 1. Check power to the thermostat 2. Check wiring diagrams Thermostat Dead 3. Check thermost

Page 8

1166 HEAT PUMP CROSS REFERENCE GUIDE RC-100BZ R (1) G (2) O (3) B (4) C (5) Y (6) W2 (7) X2 CARRIER, PAYNE DAY&NIGHT R G O C Y1 W2 L TRANE R

Page 9

22 Removing an existing thermostat 1. Disconnect the power to the control transformer. 2. Remove the cover to the existing thermostat. 3. Disconne

Page 10

33 Connect each wire to the terminal strip on the thermostat base per the wiring diagram for your system application - See Figures 4 - 5. Form the

Page 11

44 TYPICAL WIRING DIAGRAMS CAUTION: Be sure to disconnect the power to the control transformer before removing or installing thermostat. Do not sho

Page 12

55 Figure 5

Page 13

66 CONFIGURING THE BACKLIGHT ON THE RC-100BZ The backlight on the RC-100BZ can be configured to one of three different modes: 1) on for 30 seconds wh

Page 14

77 POWER UP 1. Double check wiring, be sure that there are no stray wires or wire strands at the connections. 2. Connect power to the transformer

Page 15

88 00 Address If you are using Communications Mode 0 or 1, and you are installing more than one thermostat, each must be set to a consecutive addr

Page 16

99 03 Display options The thermostat can be configured to display the following attributes: 0 Celsius am/pm time format programmable 1 Fahre